Theoretical and experimental analysis of a new refrigerant mixture BY-3 was conducted based on a single-stage vapor compression refrigeration system. The water-water heat pump system used BY-3 to produce hot water when the low temperature was 20 ℃. The following results were obtained: the highest temperature at the condenser outlet reached about 85 ℃; when the difference between the water temperatures at the condenser outlet and the evaporator inlet was less than 40 ℃, the coefficient of performance (COP) was larger than 4; when the difference reached 55 ℃, the COP still kept 3; the discharge temperature of BY-3 was lower than 100 ℃, and the refrigerant vapor pressure kept lower than 1.8 MPa. When the water temperature at the condenser outlet reached over 85 ℃, nearly a 5 ℃ superheating temperature was maintained. 相似文献